Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T05FR00850
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2005 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ok | |
06/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 1). Fire pump test and report required. TFC 913.5 | |
06/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Suite 1610: PreAction system test required for system in this suite. TFC 901.6 | |
06/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 6). Suite 1500: portable fire extinguisher is not mounted and is on floor. Extinguisher shall be mounted. TFC States: 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). |
|
06/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Test, repair, replace or remove heat detectors. TFC 901.6 | |
06/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | ). Baggins: Currently Class K extinguisher is on floor. This shall be mounted as per TFC requirements. TFC 906. | |
06/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Roof: Currently grease from Baggins restaurant. Is on roof. This shall be cleaned. TFC 904.11.6. |