Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - PRECAUTION AGAINST FIRE
Case Number - T05FR00850
Inspection Description - VIOL - PRECAUTION AGAINST FIRE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2005 | VIOL - PRECAUTION AGAINST FIRE | Approved | all ok | |
07/18/2005 | VIOL - PRECAUTION AGAINST FIRE | Violation | 2). Suite 1850: Ceiling clearance of 2 feet and clearance of 18 inches shall be maintained from sprinkler heads. Also aisle of 28 inches shall be maintained in storage room. TFC 315.2.1 3). Suite 1600. The following repairs shall be completed on pre action test report: CIF room: Head obstructed by cable tray, missing escutcheon in large room, and head to low in larger room. Report enclosed. 901.6 |
|
06/10/2005 | VIOL - PRECAUTION AGAINST FIRE | Violation | 4). Suite 1850: Boxes and storage are within 18 inches from ceiling and within 18 inches from sprinkler head. TFC states: 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. |
|
06/10/2005 | VIOL - PRECAUTION AGAINST FIRE | Violation | Suite 1500: Storage shall be within 2 feet from ceiling. TFC 315.2.1 | |
06/10/2005 | VIOL - PRECAUTION AGAINST FIRE | Violation | ). Suite 1200: remove storage from within 2 feet from ceilings. TFC 315.2.1 |