Case: T05FR00789

Parcel: 13216641A


Addresses:

763 E MACARTHUR CI


Inspection Status: Approved

Inspection History: VIOL - HIGH PILED COMBUSTIBLES

Case Number - T05FR00789

Inspection Description - VIOL - HIGH PILED COMBUSTIBLES

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2005 VIOL - HIGH PILED COMBUSTIBLES Approved ok
05/31/2005 VIOL - HIGH PILED COMBUSTIBLES Violation 4). Currently aisles have storage and machinery obstructing width. TFC states:
2305.4 Aisle maintenance. When restocking is not being conducted, aisles shall be kept clear of storage, waste material and debris. Fire department access doors, aisles and exit doors shall not be obstructed. During restocking operations using manual stocking methods, a minimum unobstructed aisle width of 24 inches (610 mm) shall be maintained in 48-inch (1219 mm) or smaller aisles, and a minimum unobstructed aisle width of one-half of the required aisle width shall be maintained in aisles greater than 48 inches (1219 mm). During mechanical stocking operations, a minimum unobstructed aisle width of 44 inches (1118 mm) shall be maintained in accordance with Section
2306.9.