Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - HIGH PILED COMBUSTIBLES
Case Number - T05FR00789
Inspection Description - VIOL - HIGH PILED COMBUSTIBLES
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2005 | VIOL - HIGH PILED COMBUSTIBLES | Approved | ok | |
05/31/2005 | VIOL - HIGH PILED COMBUSTIBLES | Violation | 4). Currently aisles have storage and machinery obstructing width. TFC states: 2305.4 Aisle maintenance. When restocking is not being conducted, aisles shall be kept clear of storage, waste material and debris. Fire department access doors, aisles and exit doors shall not be obstructed. During restocking operations using manual stocking methods, a minimum unobstructed aisle width of 24 inches (610 mm) shall be maintained in 48-inch (1219 mm) or smaller aisles, and a minimum unobstructed aisle width of one-half of the required aisle width shall be maintained in aisles greater than 48 inches (1219 mm). During mechanical stocking operations, a minimum unobstructed aisle width of 44 inches (1118 mm) shall be maintained in accordance with Section 2306.9. |