Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - WELDING & OTHER HOT WRK
Case Number - T05FR00773
Inspection Description - VIOL - WELDING & OTHER HOT WRK
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/09/2005 | VIOL - WELDING & OTHER HOT WRK | Approved | ok | |
05/26/2005 | VIOL - WELDING & OTHER HOT WRK | Violation | 3). Currently hot work is being done adjacent or close to flammable liquids and combustible material. TFC states: 2604.1.1 Combustibles. Hot work areas shall not contain combustibles or shall be provided with appropriate shielding to prevent sparks, slag or heat from igniting exposed combustibles. All hot work shall be done more in a distance of more than 30 feet from all flammable and combustible material. |
|
05/26/2005 | VIOL - WELDING & OTHER HOT WRK | Violation | Housekeeping shall be done to remove all combustible trash from building 4). Currently no portable fire extinguisher is present in building. 2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A:20-B:C rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed. |