Case: T05FR00773

Parcel: 132166190


Addresses:

850 E OHIO ST #24


Inspection Status: Approved

Inspection History: VIOL - WELDING & OTHER HOT WRK

Case Number - T05FR00773

Inspection Description - VIOL - WELDING & OTHER HOT WRK

Inspection Status - Approved

Date Description Inspector Results Comments
06/09/2005 VIOL - WELDING & OTHER HOT WRK Approved ok
05/26/2005 VIOL - WELDING & OTHER HOT WRK Violation 3). Currently hot work is being done adjacent or close to flammable liquids and combustible material. TFC states:
2604.1.1 Combustibles. Hot work areas shall not contain combustibles or shall be provided with appropriate shielding to prevent sparks, slag or heat from igniting exposed combustibles.
All hot work shall be done more in a distance of more than 30 feet from all flammable and combustible material.
05/26/2005 VIOL - WELDING & OTHER HOT WRK Violation Housekeeping shall be done to remove all combustible trash from building

4). Currently no portable fire extinguisher is present in building.
2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A:20-B:C rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed.