Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - WELDING & OTHER HOT WRK
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2005 | VIOL - WELDING & OTHER HOT WRK | Approved | all ok | |
| 05/23/2005 | VIOL - WELDING & OTHER HOT WRK | Violation | 1). Currently there is flammable liquids and combustible material in working area of hot work. All combustible and flammable liquids shall be kept back 30 feet from all hot work. TFC 2604.1 |
|
| 05/23/2005 | VIOL - WELDING & OTHER HOT WRK | Violation | 2). Extinguisher is blacked by storage. TFC requirements for portable extinguisher shall be; 2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A:20-BC rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed. Proper extinguisher shall be obtained and un obstructed |