Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
| 05/18/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.1 - Identified electrical hazards shall be abated. 1) romex from bathroom light to heater removed 2) open wiring splices outside ABS room 3) GFI needed above outside sink 605.3 - A clear working space of 30''Wx36''Dx78''H shall be maintained in front of electrical service equipment - outside NE corner 605.5 - extension cords shall not be used as a substitute for permanent wiring - trailer, ABS area 605.6 - open junction boxes shall be prohibited - blanks needed in breaker panel outside NE corner. |