Inspection Status: Approved
Inspection History: VIOL - FIRE RESIST.RATED CONST
Case Number - T05FR00701
Inspection Description - VIOL - FIRE RESIST.RATED CONST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2005 | VIOL - FIRE RESIST.RATED CONST | Approved | ok | |
06/07/2005 | VIOL - FIRE RESIST.RATED CONST | Violation | 4). Currently there are decorations hanging down from ceiling tiles, in AFNI floor these ceiling tiles are part of the fire protection system. This is in violation of TFC 703.3 703.3 Ceilings. The hanging and displaying of salable goods and other decorative materials from acoustical ceiling systems that are part of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be prohibited. |