Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T05FR00701
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2005 | INSP - FULL | Approved | all ok | |
05/18/2005 | INSP - FULL | Violation | 1). Fire sprinkler test and inspection report shall be submitted and all required repairs shall be completed. TFC 901.6 | |
05/18/2005 | INSP - FULL | Violation | 2). Fire alarm test and inspection report shall be submitted and all required repairs shall be completed. TFC 901.6 | |
05/18/2005 | INSP - FULL | Violation | 3). Fire drill shall be conducted and date shall be determined by 6-3-05. TFC 401 | |
05/18/2005 | INSP - FULL | Violation | 4). 5th floor- all banners shall be removed from ceiling grids. TFC 703.3 | |
05/18/2005 | INSP - FULL | Violation | 5). 5th floor- all decorations shall be removed from ceiling tiles- TFC 703 | |
05/18/2005 | INSP - FULL | Violation | 6). 3rd floor- ceiling tiles missing in computer room- TFC 703.1 | |
05/18/2005 | INSP - FULL | Violation | 7). 2nd floor- Exit light out of service shall be repaired. TFC 1023 | |
05/18/2005 | INSP - FULL | Violation | 8). 2nd floor- wooden pallets are within required exit width, shall be removed. TFC 1003.3.4 | |
05/18/2005 | INSP - FULL | Violation | 9). Loading dock- repair drywall-TFC 703.1 | |
05/18/2005 | INSP - FULL | Violation | 10). Quest Comm room; 3rd floor-All batteries containing sulfuric acid, which are cracked, and damaged shall be replaced, OR written documentation from manufactures explaining that damaged batteries are reliable when damaged shall be submitted to TFD. TFC 2701.3.3.2 | |
05/18/2005 | INSP - FULL | Violation | 11). TFC 604.4 Emergency power systems, including all appurtenant components shall be inspected and tested under load in accordance with NFPA 110 and NFPA 111. Exception: Where the emergency power system is used for standby power or peak load shaving, such use shall be recorded and shall be allowed to be substituted for scheduled testing of the generator set, provided that appropriate records are maintained. For your information: Tucson Fire code states: 604.2.15.1.1 Standby power loads. The following loads are classified as standby power loads: 1. Smoke control system. 2. Ventilation and automatic fire detection equipment for smokeproof enclosures. 3. Fire pumps. 4. Standby power shall be provided for elevators in accordance with Section 3003 of the International Building Code. [B] 604.2.15.1.2 Pickup time. The standby power system shall pick up its connected loads within 60 seconds of failure of the normal power supply 604.2.15.2 Emergency power. An emergency power system complying with the ICC Electrical Code shall be provided for emergency power loads as specified in Section 604.2.15.2.1. 604.2.15.2.1 Emergency power loads. The following loads are classified as emergency power loads: 1. Emergency voice/alarm communication systems. 2. Fire alarm systems. 3. Automatic fire detection systems. 4. Elevator car lighting. 5. Means of egress lighting and exit sign illumination as required by Chapter 10. |