Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2005 | INSP - FULL | Approved | ||
| 04/27/2005 | INSP - FULL | Correction Required | TFC 505.1 Address needs to be posted in front 12" letters. TFC 304.1.2 weeds in the SW part of the yard. TFC 605 Over head light remove or repair. Housekeeping TFC 315.2 Electrical cover plate for J-Box south room,Also remove extension cord leading to the trailer. TFC 605. The insulation will be tested to see if it burns,if so you will have to remove insulation.TFC 703.1,fire resistive construction in welding area.TFC 2703.3 waste oil needs to be removed,take to HHHW or take to auto parts place. |