Case: T05FR00535

Parcel: 116012300

Inspection Status: Violation

Inspection History: VIOL - CRYOGENIC FLUIDS

Date Description Inspector Results Comments
04/26/2005 VIOL - CRYOGENIC FLUIDS Violation TFC 2003 Ch 27. Haz Mat, Ch 32 Cryogenic Fluids
TABLE 2703.1.1(1)
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD
Cryogenic Fluids In use open 10 Gal or 37.785 L.
In closed system or storage 45 Gal. or 170 L
My be increased 100% if building is equipped with automatic sprinklers throughout.
Also see handout

TFC 2003 3203.4.1 Identificatrion signs
Visible hazards sign ID signs in accordance with NFPA704 shall be on the entrance to the building. Along with "NO SMOKING" signs