Case: T05FR00528

Parcel: 103175160


Addresses:

3057 N GAIA PL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T05FR00528

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/15/2005 VIOL - FIRE PROTECTION SYSTEMS Approved
04/26/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 2003 Sec. 905.2 and NFPA 14
Installation is per TFC 2003 and NFPA 14 standards
Dry standpipe is requiered where area of protection is 30' above or 150' away from the lowest level of the fire department vehicle access.

TFC 2003 Sec. 905.4.1 Protection for FDC ( Fire department connections }
Class 1 standpiipe must be protected.
Provide vehicle protection for FDC, as per Sec. 312. hand out given

TFC 2003 SEC. 901.6 Inspection, testing, and maintance.
Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
All water based extingushment system testing and maintance is based on TFC 2003 Appendix C. See atteched