Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T05FR00528
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 04/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 2003 Sec. 905.2 and NFPA 14 Installation is per TFC 2003 and NFPA 14 standards Dry standpipe is requiered where area of protection is 30' above or 150' away from the lowest level of the fire department vehicle access. TFC 2003 Sec. 905.4.1 Protection for FDC ( Fire department connections } Class 1 standpiipe must be protected. Provide vehicle protection for FDC, as per Sec. 312. hand out given TFC 2003 SEC. 901.6 Inspection, testing, and maintance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. All water based extingushment system testing and maintance is based on TFC 2003 Appendix C. See atteched |