Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | Approved | Permit pulled and sprinklers install. | |
| 04/20/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6 & 901.4 Fire protection systems. Fire protection systems shall be maintained at all times for proper coverage. The following areas shall be corrected: 1.) In main lobby 1/2" square grid suspended ceiling blocking coverage. 2.) Office next to lobby 1/2" square grid suspended ceiling blocking coverage. 3.) Men's bathroom by John Davies office 1/2" grid suspended ceiling block coverage. 4.) In John Davies office need to correct sprinkler coverage. Plans and permits needed before work is done. |