Case: T05FR00504

Parcel: 130144440


Addresses:

3950 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T05FR00504

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2005 INSP - FULL Approved Final inspection. All violations corrected.
04/19/2005 INSP - FULL Correction Required TFC 904.11.1 The actuation of commercial cooking equipment fire suppression system shall automatically shut down the fuel or electrical power to the system.need to install a microswitch to the ansul.I would like to see a schedule sheet posted.TFC904.11.6.3