Case: T05FR00473

Parcel: 12417138A


Addresses:

1070 E 20TH ST

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
04/26/2005 VIOL - BUILDING SVCS & SYSTEMS Approved
04/11/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space of not less than 30" width, 36" depth' 78" height shall be provided in front of electrical service equipment.
1. main panel east
2. disconnect on porch
3. panel inside on east wall
04/11/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Abatement of electrical hazards. Electrical wiring that is damaged shall not be used. (cord to hot plate)
04/11/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shal not be used as a substitute for permanent wiring.1. light on machine at NW corner
2. (2) cords in west room through doorway
3. cord through wall in welding area
4. cord to machine on porch (west wall)