Case: T05FR00468

Parcel: 12901044C


Addresses:

1940 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T05FR00468

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
04/22/2005 VIOL - FIRE PROTECTION SYSTEMS Approved REPAIRS MADE
04/08/2005 VIOL - FIRE PROTECTION SYSTEMS Partial Approval MAIN VALVE REPLACED AND 4" PIPE BELOW REPLACED.
SPRINKLER HEAD REPLACED IN COOLER
03/16/2005 VIOL - FIRE PROTECTION SYSTEMS Violation PER SPRINKLER INSPECTION REPORT THE FOLLOWING PROBLEMS SHALL BE TAKEN CARE OF:
1. MAIN VALE DOES NOT SHUT, NEED TO REPAIR OR REPLACE
2. REPLACE DAMAGE SPRINKLER HEAD IN BAKERY COOLER.
3. 4" PIPING BELOW MAIN SHUT OFF IS LEAKING SHALL HAVE PIPING REPLACED.
4. REPLACE MISSING CECILING TILE IN KITCHEN AREA