Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 03/18/2005 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Approved |
Sprinkler riser in place, underground psi test done at 220 for two hours, and flush done. 2 inch drain test done and water motor gong works. |
| 03/09/2005 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
TFC 903.2.10.1 Basement's. All basements over 1,500 square feet shall be sprinklered. |