Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - ADMINISTRATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/18/2005 | VIOL - ADMINISTRATION | Approved | Sprinkler riser in place and all testing done. | |
| 03/09/2005 | VIOL - ADMINISTRATION | Violation | TFC 109.2 Notice of Violation Under the TFC 903.2.10.1 Basement's" states all basements over 1,500 square feet shall be sprinklered. All piping is installed per plans but no riser is installed. Sprinkler system in basement is not operational and not approved. TFC 110.1 Unsafe Conditions Basement area is found unsafe to use. As of today 03/09/2005, you are hereby order not to use basement for any activities or for storage. Need to remove all chairs and other materials from basement and leave it empty until all finals for C of O and sprinkler system has been approved. |