Case: T05FR00399

Parcel: 134220130


Addresses:

6700 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - ADMINISTRATION

Date Description Inspector Results Comments
03/18/2005 VIOL - ADMINISTRATION Approved Sprinkler riser in place and all testing done.
03/09/2005 VIOL - ADMINISTRATION Violation TFC 109.2 Notice of Violation
Under the TFC 903.2.10.1 Basement's" states all basements over 1,500 square feet shall be sprinklered. All piping is installed per plans but no riser is installed. Sprinkler system in basement is not operational and not approved.

TFC 110.1 Unsafe Conditions
Basement area is found unsafe to use.

As of today 03/09/2005, you are hereby order not to use basement for any activities or for storage. Need to remove all chairs and other materials from basement and leave it empty until all finals for C of O and sprinkler system has been approved.