Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/18/2005 | INSP - FULL | Violation | 1). Currently paper products are being stored adjacent to electrical boxes. 30 inch working space shall be around all electrical service equip. TFC 605.3 2). Extension cord to fans is damaged and shall be repaired or discarded TFC 605.1 3). Currently portable fire extinguishers are not mounted. Fire extinguishers shall be mounted according to TFC 906.9, which states: 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). 4). Currently aisle width id non-existant in area of corn storage. Aisles shall be 28 inches in this area. TFC 1013.4.1 |