Case: T05FR00378

Parcel: 129042660


Addresses:

323 S NORRIS AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T05FR00378

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/16/2005 INSP - FULL Approved 2003 TFC-3401.4 Permits shall be required to have the AST removed.
TFC- 2703.2.6.1 Tanks out of sevice for a period of 90 days shall properly safeguarded or removed in an approved manner.
Air Proucts came and removed the tank properly, they installered and are the owners of the the tank.09/15/05. No further action required.
03/16/2005 INSP - FULL Approved multiplug adapter in office shall remove or replace with power surge protector.TFC 605.4 Freezer lights need the light cover protection.TFC605.5.1 Back door needs the exit sign. TFC1006.1 The middle freezer need the light switch repaired.TFC605.6. The 5000 gal. liquid nitrogen tank needs a permit.TFC105.7.2.