Case: T05FR00377

Parcel: 12619188Z


Addresses:

4425 E 22ND ST


Inspection Status: Approved

Inspection History: COMPL - INITIAL INSPECTION

Case Number - T05FR00377

Inspection Description - COMPL - INITIAL INSPECTION

Inspection Status - Approved

Date Description Inspector Results Comments
03/21/2005 COMPL - INITIAL INSPECTION Approved On March 21, 2005, a fire prevention inspection was conducted at The Palm Court Inn, 4425 East 22nd.

Thank you for your efforts in smoke detector maintenance. The reports have been received.
03/21/2005 COMPL - INITIAL INSPECTION Violation 1). All electrical rooms have either holes in the wall and (or) ceilings these must be repaired with approved dry wall. TFC 703.1
03/21/2005 COMPL - INITIAL INSPECTION Violation 2). Dry standpipe outlet is missing turn valve. This must be replaced. TFC 901.6
03/21/2005 COMPL - INITIAL INSPECTION Violation 3). Fire department connection to dry standpipe must be labeled "FIRE DEPT CONNECTION" .TFC 901.6
03/21/2005 COMPL - INITIAL INSPECTION Violation 4). Exit signs by the following apts. Are out of service and shall be repaired. 435, 458 TFC 1026.3
03/21/2005 COMPL - INITIAL INSPECTION Violation 5). Hole in second floor ceiling by Apt 222 must be repaired TFC 703.1
03/16/2005 COMPL - INITIAL INSPECTION Correction Required Smoke detector safety issues.