Inspection Status: Approved
Inspection History: VIOL - CRYOGENIC FLUIDS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/08/2005 | VIOL - CRYOGENIC FLUIDS | Approved | ||
| 03/09/2005 | VIOL - CRYOGENIC FLUIDS | Violation | TFC 2000 105.6.11 premit for cryognics 105.6.11 Cryogenic fluids. An operational permit is required to produce, store, transport on site, use, handle or dispense cryogenic fluids in excess of the amounts listed in Table 105.6.11. Indoors, 10 gal- outdoors, 55 gal TFC 2000 max storage of cryogenics indoors with a permit is 45 gal (170 l) 1.Remove, or reduce to 10 gal , or gain a permit for storage and use over 10 gal. |
|
| 03/09/2005 | VIOL - CRYOGENIC FLUIDS | Violation | TFC 2000 3203.4.1 Identification signs. Visible hazard identification signs in accordance with NFPA704 shall be provided at entrances to buildings or areas in which cryogenic fluids are stored, handled or used. 3203.4.2 Identification of contents. Stationary and portable containers shall be marked with the name of the gas contained. 3203.5.2 Securing of containers. Portable containers subject to shifting or upset shall be secured. 3203.6 Separation from hazardous conditions. Cryogenic containers and systems in storage or use shall be separated from materials and conditions which pose exposure hazards to or from each other TABLE 3203.6.2 SEPARATION OF PORTABLE CONTAINERS FROM EXPOSURE HAZARDS EXPOSURE MINIMUM DISTANCE (feet) Building exits 10 Wall openings 1 Air intakes 10 Lot lines 5 Room or area exits 3 Combustible materials such as paper, leaves, weeds, dry grass or debris 15 Other hazardous materials In accordance with Chapter 27 |