Inspection Status: Approved
Inspection History: COMPL - INITIAL INSPECTION
Case Number - T05FR00345
Inspection Description - COMPL - INITIAL INSPECTION
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2005 | COMPL - INITIAL INSPECTION | Approved | occuapnt load confirmed by approved plans | |
| 03/04/2005 | COMPL - INITIAL INSPECTION | Violation | On 2-17-05 a fire prevention inspection in regards to occupant load was conducted on the 5th floor of 333 East Wetmore Rd, In Tucson, Arizona. On that date, 260 occupants were counted on the 5th floor. Building engineering supplied a square footage of 24, 500 for the entire unseperated 5th floor. The attached letter is your fire inspection report. In summary, the following Tucson Fire Code Violation(s) was noted: Tucson Fire Code sections and table 1004.1.2 states: The maximum floor area allowed per occupant is 100 sq. feet per occupant, for a business type area. With the occupant number of 260, and the square footage supplied by the building representative at 24, 500, you are exceeding the occupant load for a business type area on the 5th floor. With the above numbers, this occupant load if remain a business type area, shall be 240. |