Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T05FR00296
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2005 | VIOL - FIRE PROTECTION SYSTEMS | Approved | All repairs made and stock lowered. | |
| 02/28/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6 Fire protection systems. Fire sprinkler systems shall be maintain at all times. Shall repair or replace the following problems: 1.) By toilet display booth shall replace both viking concealer cover plates. At no time can plates be painted by owner. Cover plates can only be painted by factory for there U/L listing. Can remove paint must get new ones. 2.) Storage in back stock room shall be lowered 18" below sprinkler heads. 3.) Shall repair or replace water motor gong. According to sprinkler report WMG failed to work. |