Case: T05FR00276

Parcel: 13013059A


Addresses:

3801 E 34TH ST


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T05FR00276

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/24/2005 VIOL - FIRE PROTECTION SYSTEMS Correction Required Received report from United fire stating they have removed the water motor gong and rplace it with a electric bell. Called mike Oaks of Old Pueblo Traders asked if United fire wired the bell on a dedicated circuit, he did not know but will get back with about it. I advised him that I will need to see the bell work and make sure it is wired right.
02/24/2005 VIOL - FIRE PROTECTION SYSTEMS Approved Inspection test was done on alarm bell no problems.
02/04/2005 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 Fire protection systems. Fire sprinkler systems shall be maintian at all times.
Received sprinkler report from united fire stating the following:
1. Horizontal post indicating valve seems to have not been installed correctly. No bolts in the outside plate.
2. Water gong non operable leaking retard chamber.