Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T05FR00276
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/24/2005 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Received report from United fire stating they have removed the water motor gong and rplace it with a electric bell. Called mike Oaks of Old Pueblo Traders asked if United fire wired the bell on a dedicated circuit, he did not know but will get back with about it. I advised him that I will need to see the bell work and make sure it is wired right. | |
02/24/2005 | VIOL - FIRE PROTECTION SYSTEMS | Approved | Inspection test was done on alarm bell no problems. | |
02/04/2005 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 901.6 Fire protection systems. Fire sprinkler systems shall be maintian at all times. Received sprinkler report from united fire stating the following: 1. Horizontal post indicating valve seems to have not been installed correctly. No bolts in the outside plate. 2. Water gong non operable leaking retard chamber. |