Case: T05FR00246

Parcel: 13411359B


Addresses:

8101 E 22ND ST

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
02/01/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Electrical hazards shall be abated.
1. extension cord used as permanent wiring (treatment room).
2. unapproved wiring to lights under front awning.
3. receptacle on outside wall (west) not weatherproof.
4. unapproved wiring to lights under west island awning.
02/01/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
1. office
2. west island awning
02/01/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring.
1. extension cord in lobby at ceiling.
2. extension cord in H2o treatment room.
02/01/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Open junction boxes and open wiring splices shall be prohibited.
1. H2O treatment room
2. west island awning