Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T05FR00244
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/23/2005 | VIOL - MEANS OF EGRESS | Approved | New doors installed. | |
02/15/2005 | VIOL - MEANS OF EGRESS | Violation | TFC 1005 or 1026.7 exiting. The minimum width of each door opeing shall sufficient for occupant load thereof shall provide a clear eidth of not less than 28 inches. TFC 1008.1.8.3 Locks and latches TFC 1008.1.8.4 Bolt Locks Manually operated flush bolts or surface bolts are not permitted. 1. Both rear exit doors are not the proper width. 2. Both rear exit doors need proper locking devices. South door has double cylinder keyed dead bolt. North door has a bolt lock. C of O was held up until repairs are made. |