Case: T05FR00144

Parcel: 125110590


Addresses:

3566 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T05FR00144

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2005 VIOL - FIRE PROTECTION SYSTEMS Approved All repairs made
02/02/2005 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Fire protection systems. Fire sprinkler systems shall be maintain at all times. The following problems were found with your sprinkler system and shall be repaired.
1.) Replace broken FDC cap (auto repair shop riser)
2.) In paint spary booth need to cover all sprinkler heads with plastic bags to keep overspary off heads. Need to change bags as they get over spsary on them.
3.) Replace painted sprinkler head under stairs, in parts storage area.
4.) *Correct sprinkler coverage in back storage room.
5.) Correct sprinkler coverage on 2nd level storage area. Ceiling was removed so heads are to far from deck.
6.) Replace dented sprinkler head under canopy - (westside outside service wall)

*You will need a Lic. Sprinkler contactor to install sprinkler heads in back storage area. You will need approved plans and permits before work is done.