Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T05FR00144
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/22/2005 | VIOL - FIRE PROTECTION SYSTEMS | Approved | All repairs made | |
02/02/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Fire protection systems. Fire sprinkler systems shall be maintain at all times. The following problems were found with your sprinkler system and shall be repaired. 1.) Replace broken FDC cap (auto repair shop riser) 2.) In paint spary booth need to cover all sprinkler heads with plastic bags to keep overspary off heads. Need to change bags as they get over spsary on them. 3.) Replace painted sprinkler head under stairs, in parts storage area. 4.) *Correct sprinkler coverage in back storage room. 5.) Correct sprinkler coverage on 2nd level storage area. Ceiling was removed so heads are to far from deck. 6.) Replace dented sprinkler head under canopy - (westside outside service wall) *You will need a Lic. Sprinkler contactor to install sprinkler heads in back storage area. You will need approved plans and permits before work is done. |