Inspection History Details
Inspection Status: Compliance
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T05FR00121
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/27/2005 | VIOL - FIRE PROTECTION SYSTEMS | Compliance | Reinspection made all repairs made. | |
01/03/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6 Fire protection systems. Fire sprinkler systems shall be maintain at all times. Shall repair sprinkler coverage front lobby area. Shall remove one of two sprinkler heads to close together. Shall repair packing on main shut offs. Shall have sprinkler head on westside of office lowered, sprinkler heads can be above ceciling. |
|
01/02/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Recived report problems noticed, new feild notice given. | |
12/27/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6 Fire protection systems. Fire sprinkler systems shall be inspected annually. |