Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T05FR00069
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/12/2005 | INSP - FULL | Approved | all ok, waiting for fire pump report | |
02/28/2005 | INSP - FULL | Approved | ||
02/28/2005 | INSP - FULL | Approved | ||
01/18/2005 | INSP - FULL | Violation | 1). Fire alarm test and inspection report shall be submitted, with all required repairs completed. TFC 901.6 | |
01/18/2005 | INSP - FULL | Violation | 2). Fire sprinkler test and inspection report shall be submitted, with all required repairs completed. TFC 901.6 | |
01/18/2005 | INSP - FULL | Violation | 3). Fire test report shall be submitted with all required repairs completed. TFC 901.6 | |
01/18/2005 | INSP - FULL | Violation | 4). Fire warden meeting is scheduled for 3-18-05 at 10:30 a.m. | |
01/18/2005 | INSP - FULL | Violation | 5). Fire drill scheduled for 3-22-05 at 10 a.m. | |
01/18/2005 | INSP - FULL | Violation | 6). Fusible link in main electrical is blocked by filter, shall be repaired, by moving filter. TFC 703.1 | |
01/18/2005 | INSP - FULL | Violation | 7). Currently unused cardboard boxes are on rafters in elevator room. All cardboard boxes shall be removed from elevator room. TFC 315.3 | |
01/18/2005 | INSP - FULL | Violation | 8). Suite 900- Currently waste paper storage is obstructing exit width. These shall be removed to provide adequate exit width. TFC 1027.2 | |
01/18/2005 | INSP - FULL | Violation | 9). Log of weekly test of emergency generator shall be initiated. TFC 604.3.2. | |
01/18/2005 | INSP - FULL | Violation | 10). Suite 730- Ceiling tiles are missing TFC 703.1, Electrical face plate shall be reinstalled TFC 605.1, complete fire stopping with approved material above missing ceiling tiles- TFC 703.1.1 | |
01/18/2005 | INSP - FULL | Violation | 11). Suite 300 and D &B Offices. Currently plants and other decorative materials are hanging on ceiling tiles and grid supports. These ceiling tiles and supports are fire resistive and are part of the fire protection system. All shall be removed as per TFC 703.3, which states; 703.3 Ceilings. The hanging and displaying of salable goods and other decorative materials from acoustical ceiling systems that are part of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be prohibited. All of these items shall be removed. |
|
01/18/2005 | INSP - FULL | Violation | 12). Suite 300: Pre-Action system shall be tested and repaired in required. Report shall be submitted to TFD. TFC 901.6 |