Case: T05FR00069

Parcel: 128100540


Addresses:

5210 E WILLIAMS CI


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T05FR00069

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2005 INSP - FULL Approved all ok, waiting for fire pump report
02/28/2005 INSP - FULL Approved
02/28/2005 INSP - FULL Approved
01/18/2005 INSP - FULL Violation 1). Fire alarm test and inspection report shall be submitted, with all required repairs completed. TFC 901.6
01/18/2005 INSP - FULL Violation 2). Fire sprinkler test and inspection report shall be submitted, with all required repairs completed. TFC 901.6
01/18/2005 INSP - FULL Violation 3). Fire test report shall be submitted with all required repairs completed. TFC 901.6
01/18/2005 INSP - FULL Violation 4). Fire warden meeting is scheduled for 3-18-05 at 10:30 a.m.
01/18/2005 INSP - FULL Violation 5). Fire drill scheduled for 3-22-05 at 10 a.m.
01/18/2005 INSP - FULL Violation 6). Fusible link in main electrical is blocked by filter, shall be repaired, by moving filter. TFC 703.1
01/18/2005 INSP - FULL Violation 7). Currently unused cardboard boxes are on rafters in elevator room. All cardboard boxes shall be removed from elevator room. TFC 315.3
01/18/2005 INSP - FULL Violation 8). Suite 900- Currently waste paper storage is obstructing exit width. These shall be removed to provide adequate exit width. TFC 1027.2
01/18/2005 INSP - FULL Violation 9). Log of weekly test of emergency generator shall be initiated. TFC 604.3.2.
01/18/2005 INSP - FULL Violation 10). Suite 730- Ceiling tiles are missing TFC 703.1, Electrical face plate shall be reinstalled TFC 605.1, complete fire stopping with approved material above missing ceiling tiles- TFC 703.1.1
01/18/2005 INSP - FULL Violation 11). Suite 300 and D &B Offices. Currently plants and other decorative materials are hanging on ceiling tiles and grid supports. These ceiling tiles and supports are fire resistive and are part of the fire protection system. All shall be removed as per TFC 703.3, which states;

703.3 Ceilings. The hanging and displaying of salable goods and other decorative materials from acoustical ceiling systems that are part of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be prohibited.

All of these items shall be removed.
01/18/2005 INSP - FULL Violation 12). Suite 300: Pre-Action system shall be tested and repaired in required. Report shall be submitted to TFD. TFC 901.6