01/27/2005 INSP - FULL Approved
01/14/2005 INSP - FULL Approved 1). Currently LPG heating device is allowed, only if tank is 2.5 water gallons. Currently tank is 5 gallons. TFC 3803.2.1.6 states;

3803.2.1.6 Use with self-contained torch assemblies.
Portable LP-gas containers are allowed to be used to supply approved self-contained torch assemblies or similar appliances. Such containers shall not exceed a water capacity of 2.5 pounds (1 kg).