Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T05FR00050
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/27/2005 | INSP - FULL | Approved | ||
01/27/2005 | INSP - FULL | Approved | ||
01/13/2005 | INSP - FULL | Violation | 1) Currently many empty containers exist in ink close room, workshop floor, and rear of building. Empty containers must be free of vapors, or shall be counted as full. 3404.3.3.4 Empty containers or portable tank storage. The storage of empty tanks and containers previously used for the storage of flammable or combustible liquids, unless free from explosive vapors, shall be stored as required for filled containers and portable tanks. Portable tanks and containers, when emptied shall have the covers or plugs immediately replaced in openings. |
|
01/13/2005 | INSP - FULL | Violation | 2). Portable fire extinguisher shall be required as per TFC 906. |