Case: T05FR00050

Parcel: 12407220B


Addresses:

110 S PARK AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T05FR00050

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
01/27/2005 INSP - FULL Approved
01/27/2005 INSP - FULL Approved
01/13/2005 INSP - FULL Violation 1) Currently many empty containers exist in ink close room, workshop floor, and rear of building. Empty containers must be free of vapors, or shall be counted as full.
3404.3.3.4 Empty containers or portable tank storage.
The storage of empty tanks and containers previously used for the storage of flammable or combustible liquids, unless free from explosive vapors, shall be stored as required for filled containers and portable tanks. Portable tanks and containers, when emptied shall have the covers or plugs immediately replaced in openings.
01/13/2005 INSP - FULL Violation 2). Portable fire extinguisher shall be required as per TFC 906.