Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 01/04/2005 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
TFC 901.6- Fire extinguishers shall be maintained in operative condition at all times. |
| 01/04/2005 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
TFC 906.5- Extinguishers shall be located in a conspicuous location where they can be readily available. |
| 01/04/2005 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
TFC 906.7- Portable fire extinguishers shall be installed on their hangers or brackets. See handout. |
| 01/04/2005 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
TFC 901.6.2- Records of all system inspections, tests and maintenance required shall be maintained on the premises for a minimum of 3 years. |