Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T05EL02516
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/02/2006 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
01/24/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE HAS TO BE GROUNDED WITH 2 GROUND ROCKS 6' SPORT WITH A #4 BARE COPPER, INCLUDING WATER BOND 2. CANNOT USE A SQUARE"D" BREAKER - MUST BE MURRAY AND 20 AMP 3. EXISTING J-BOX MUST BE WEATHERPROOF - 4. USE WIRE NUTS TO SPLICE WIRING IN OLD FUSE BOX 5. AS RISER GOES THRU ROOF - CONDUIT MUST HAVE A ROOF JACK & SEAL OUT 6. TAPE NEUTRAL WHITE AT WEATHER HEAD |
|