Permit: T05EL02510

Parcel: 117032760


Addresses:

737 N 6TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL02510

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/29/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CLEAN PIPE WHERE GAS CLAMP IS ATTACHED
2) INSTALL BOND BUSHING WHERE REDUCING WASHER IS USED
3) INSTALL PROPER COVER FOR GFI AT PANEL
4) NEED PROPER TRANSITION FROM U.F. CABLE TO 3/4" EMT
5) GET ALL OTHER PERMITS FOR NEW WORK (MECHANICAL, PLUMBING, ETC...)
6) REMOVE OLD 2" RISER
12/28/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*