Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL02510
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/03/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/29/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CLEAN PIPE WHERE GAS CLAMP IS ATTACHED 2) INSTALL BOND BUSHING WHERE REDUCING WASHER IS USED 3) INSTALL PROPER COVER FOR GFI AT PANEL 4) NEED PROPER TRANSITION FROM U.F. CABLE TO 3/4" EMT 5) GET ALL OTHER PERMITS FOR NEW WORK (MECHANICAL, PLUMBING, ETC...) 6) REMOVE OLD 2" RISER |
|
12/28/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |