Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL02506
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR INCREASE |
|
| 12/28/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROPERLY SUPPORT RISER ABOVE PANEL 2) INSTALL GROUNDING ELECTRODE CONDUCTOR BEHIND PIPING AND TO STRUCTURE. GROUNDING ELECTRODE TO BE AS CLOSE AS POSSIBLE TO SERVICE 250.30(A)(4) 3) SUPPORT CONDUITS AND TIGHTEN LOOSE FITTINGS 4) GROUND JUNCTION BOXES 5) MISSING LB COVER 6) APPROVED FITTINGS AND SEALING DEVICES NEEDED 7) PLEASE LABEL ALL BREAKERS 8) OLD DISCONNECT NOT TO BE USED AT JUNCTION BOX 9) FITTING TO BE FOR WEATHER PROOF LOCATION |