Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/05/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NOTES: 1. INSTALL BOND BUSHINGS OR BONDING LOCKNUTS ON ALL NIPPLES AHEAD OF OVERCURRENT DEVICES. 2. INSTALL MAIN BOND JUMPER IN CT CAN OR GUTTER. 3. INSTALL GREEN BOND SCREWS IN DISCONNECTS AT SERVICE. 4. COMPLETE WIRING OF SERVICE AND DISCONNECTS. 5. PROVIDE PLANS/PERMIT & PAST INSPECTION REPORTS. |