Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/16/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) SUPPORT CONDUIT AT SIDE OF PANEL
2) SUPPORT RISER AND METER SOCKET
3) PROTECT NM CABLE FROM WEATHER
4) FILL UN USE PORTION OF OPENING WITH A NON COMBUSTIBLE PRODUCT
5) INSTALL HOOD
6) PLEASE PROVIDE GFCI PROTECTION AT BATHROOMS
7) BRING SWITCH OUT OF WALL (BATHROOM)
8) WE HAVE GROUNDED RECEPTACLE ON AN UNGROUNDED SYSTEM
9) SMOKE DETECTORS NEEDED IN BEDROOMS
10) PROTECT BULB IN CLOSET
11) PLEASE OBTAIN THE SERVICES OF A LICENSED ELECTRICAL CONTRACTOR TO PERFORM WORK