Permit: T05EL02472

Parcel: 11623155E


Addresses:

601 W SIMPSON ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T05EL02472

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
01/20/2006 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
NOTES: 1) J-BOX IN BACK OF TENT WILL NEED TO BE ELEVATED 1" TO 2" ABOVE GRADE TO PREVENT WATER RUN OFF FROM ENTERING
2) WILL CLEAR SERVICE FOR POWER UPON RECEIPT OF LETTER FROM ENGINEER APPROVING CHANGE FOR 500 MCM INSTALL AT SERVICE
01/19/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLAN CALLS FOR 500 MCM CONDUCTORS FROM CT CAN TO 400 A DISCON'S
2. GROUND WIRES TO BUSHINGS IN 400 AMP DISCONNECT PER TABLE 250-122 NEED TO BE #3 COPPER, SAME AS GROUNDS TO BUSHINGS ON CONDUITS ENTERING TRANS.
3. TRANSFORMER CALLS OUT A 3/0 COPPER TO TWO GROUND RODS
4. AT TRANSFORMER SECONDARY CONDUITS EACH BUSHING NEEDS A #6 TO GROUND BAR AS IN GUTTER OR SIZE ONE FOR ALL
5. J BOX ON EAST SIDE OF TENT - CONDUCTORS LEFT CUT - NO TAPED OR ISOLATED - I PRESUME TO BE CONNECTED AT LATER DATE.
PLEASE INSTALL AS PER PLAN SINCE THEY HAVE BEEN DRAWN BY AN EE AND APPROVED BY OFFICE THAT WAY.
01/18/2006 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
INSTALL NEUTRALS IN SERVICE DISCONNECTS & BOND PER 250. 24. B NOT SHOWN ON PLAN BUT REQUIRED BY NEC.
WHEN EQUIP. GROUND IS DAISY CHAINED TO ALL BOND BUSHINGS, IT MUST BE SIZED ACCORDING TO THE SUN OF ALL PARALLED CONDUCTORS & TABLE 250.122
INSTALL FUSES & R-PINS