Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T05EL02472
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* NOTES: 1) J-BOX IN BACK OF TENT WILL NEED TO BE ELEVATED 1" TO 2" ABOVE GRADE TO PREVENT WATER RUN OFF FROM ENTERING 2) WILL CLEAR SERVICE FOR POWER UPON RECEIPT OF LETTER FROM ENGINEER APPROVING CHANGE FOR 500 MCM INSTALL AT SERVICE |
|
| 01/19/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLAN CALLS FOR 500 MCM CONDUCTORS FROM CT CAN TO 400 A DISCON'S 2. GROUND WIRES TO BUSHINGS IN 400 AMP DISCONNECT PER TABLE 250-122 NEED TO BE #3 COPPER, SAME AS GROUNDS TO BUSHINGS ON CONDUITS ENTERING TRANS. 3. TRANSFORMER CALLS OUT A 3/0 COPPER TO TWO GROUND RODS 4. AT TRANSFORMER SECONDARY CONDUITS EACH BUSHING NEEDS A #6 TO GROUND BAR AS IN GUTTER OR SIZE ONE FOR ALL 5. J BOX ON EAST SIDE OF TENT - CONDUCTORS LEFT CUT - NO TAPED OR ISOLATED - I PRESUME TO BE CONNECTED AT LATER DATE. PLEASE INSTALL AS PER PLAN SINCE THEY HAVE BEEN DRAWN BY AN EE AND APPROVED BY OFFICE THAT WAY. |
|
| 01/18/2006 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* INSTALL NEUTRALS IN SERVICE DISCONNECTS & BOND PER 250. 24. B NOT SHOWN ON PLAN BUT REQUIRED BY NEC. WHEN EQUIP. GROUND IS DAISY CHAINED TO ALL BOND BUSHINGS, IT MUST BE SIZED ACCORDING TO THE SUN OF ALL PARALLED CONDUCTORS & TABLE 250.122 INSTALL FUSES & R-PINS |