Permit: T05EL02467

Parcel: 111070160


Addresses:

3434 E WATER ST #24


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL02467

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
06/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL GROUND WIRES CANNOT TIE TOGETHER USE A GROUND BAR.
2. 30-AMP CIRCUIT BREAKER FOR COOLER TO BE 20 AMPS.
05/30/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDS & NEUTRALS TO BE SEPARATED AT PANEL.
2. SEAL HOLE BOTTOM OF PANEL.
3. 30 AMP. CIRCUIT BREAKER WITH #12 WIRE S/B 20 AMP.
4. NEED A MAIN BREAKER.
5. OUTSIDE CONDUIT MUST USE COMPRESSION FITTING NOT SET SCREW.
6. PVC CONDUIT TO BE SCHEDULE 80
7. SUPPORT ALL CONDUIT USED OUTSIDE OF PANEL.
8. PVC CONDUIT RUN INTO BOTTOM OF SERVICE BROKEN CONCENTRIC KO - USE REDUCING WASHERS.
9. ANGLE FITTINGS NOT APPROVED FOR OUTSIDE.