Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL02467
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL GROUND WIRES CANNOT TIE TOGETHER USE A GROUND BAR. 2. 30-AMP CIRCUIT BREAKER FOR COOLER TO BE 20 AMPS. |
|
| 05/30/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDS & NEUTRALS TO BE SEPARATED AT PANEL. 2. SEAL HOLE BOTTOM OF PANEL. 3. 30 AMP. CIRCUIT BREAKER WITH #12 WIRE S/B 20 AMP. 4. NEED A MAIN BREAKER. 5. OUTSIDE CONDUIT MUST USE COMPRESSION FITTING NOT SET SCREW. 6. PVC CONDUIT TO BE SCHEDULE 80 7. SUPPORT ALL CONDUIT USED OUTSIDE OF PANEL. 8. PVC CONDUIT RUN INTO BOTTOM OF SERVICE BROKEN CONCENTRIC KO - USE REDUCING WASHERS. 9. ANGLE FITTINGS NOT APPROVED FOR OUTSIDE. |