Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/27/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*LETTER OF OWNERSHIP NOT CORRECT, NEEDS TO STATE WHO CURRENT OWNER IS |
|
| 01/05/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* #1 THE #4 GROUND WIRE GOES ON OTHER SIDE OF BARREL GROUND ROD CLAMP NOT BOLT SIDE. #2 WATER & GAS BOND MISSING #3 TOP UNISTRUT SUPPORT PULLED AWAY FROM WALL #4 SEAL OR ROOF CEMENT ROOF JACK #5 PROVIDE NAME OF LIC. ELECTRICAL CONTRACTOR |