Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL02429
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/13/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES 1. USE SPLIT BOLT OR CRIMP TO BOND GROUND ELECTRODE CONDUCTORS TOGETHER OUTSIDE OF SERVICE EQUIP. DO NOT GROUND 2ND SERVICE FROM GROUND BAR OF 1ST SERVICE. 2. J-BOX ABOVE SERVICES MUST BE NEMA 3R TYPE 3. PERMIT DESCRIPTION MUST BE CHANGED TO 125 AMP |