Permit: T05EL02429

Parcel: 124090850


Addresses:

1748 E 9TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL02429

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/16/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/13/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES
1. USE SPLIT BOLT OR CRIMP TO BOND GROUND ELECTRODE CONDUCTORS TOGETHER OUTSIDE OF SERVICE EQUIP. DO NOT GROUND 2ND SERVICE FROM GROUND BAR OF 1ST SERVICE.
2. J-BOX ABOVE SERVICES MUST BE NEMA 3R TYPE
3. PERMIT DESCRIPTION MUST BE CHANGED TO 125 AMP