Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) ALTHOUGH WIRING HAS COVERED AT INSPECTION, A VISUAL INSPECTION HAS BEEN MADE AND ELECTRICAL CONTRACTOR HAS INSTALLED ARC FAULT BREAKERS ON ALL BRANCH CIRCUITS FOR ADDED SAFETY (BREAKERS TO REMAIN) |
|
| 08/17/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* I CONSIDER THIS UNIT TO BE A DWELLING PLANS MUST REFLECT THAT AND UNIT MUST BE WIRED PER NEC REQUIREMENTS FOR A DWELLING INTERIOR WIRING COVERED AT INSPECTION AND WILL NEED TO BE REOPENED OR ARC FAULT PROTECTED OR PERHAPS A MEG TEST CERTIFIED BY ELECTRICAL CONTRACTOR. |
|
| 04/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ADD ALL NEW WIRING TO PERMIT. 2. BOND ALL METALLIC PIPING TO SERVICE. 3. COULD NOT LOCATE GROUND RODS. 4. BRANCH CKTS NEED TO BE DERATED. 5. PANEL DIRECTORY NOT COMPLETE. 6. PROVIDE LEVEL WORKING AREA 36" IN FRONT OF SERVICE. 7. NOT A COMPLETE INSPECTION AT THIS TIME (SEE#1) 8. SECURE G.E.C. TO BUILDING. |