Permit: T05EL02419

Parcel: 113020450


Addresses:

1147 E KNOX DR #02

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/29/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) ALTHOUGH WIRING HAS COVERED AT INSPECTION, A VISUAL INSPECTION HAS BEEN MADE AND ELECTRICAL CONTRACTOR HAS INSTALLED ARC FAULT BREAKERS ON ALL BRANCH CIRCUITS FOR ADDED SAFETY (BREAKERS TO REMAIN)
08/17/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
I CONSIDER THIS UNIT TO BE A DWELLING
PLANS MUST REFLECT THAT AND UNIT MUST BE WIRED PER NEC REQUIREMENTS FOR A DWELLING
INTERIOR WIRING COVERED AT INSPECTION AND WILL NEED TO BE REOPENED OR ARC FAULT PROTECTED OR PERHAPS A MEG TEST CERTIFIED BY ELECTRICAL CONTRACTOR.
04/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ADD ALL NEW WIRING TO PERMIT.
2. BOND ALL METALLIC PIPING TO SERVICE.
3. COULD NOT LOCATE GROUND RODS.
4. BRANCH CKTS NEED TO BE DERATED.
5. PANEL DIRECTORY NOT COMPLETE.
6. PROVIDE LEVEL WORKING AREA 36" IN FRONT OF SERVICE.
7. NOT A COMPLETE INSPECTION AT THIS TIME (SEE#1)
8. SECURE G.E.C. TO BUILDING.