Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2006 | ELECTRIC - RECONNECT | Approved | ||
| 01/09/2006 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :$ CONTRACTOR DOESN'T HAVE ALL REQUIRED PERMITS AS WAS ADVISED AT LAST INSPECTION | |
| 12/07/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ANTI-OXIDATION PASTE ON ALL ALUM. TERMINATIONS. 2. SEAL OPEN BREAKER SPACES AT SERVICE PANEL. 3. INSTALL FHA STRAPS AS DISCUSSED 4. REMOVE DOUBLE LUGGING AT PANEL. 5. NOTE - NEED PERMITS FOR PLUMBING, MECH, ELEC, ETC. (REMODEL GOING ON) |