Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/09/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ANSWER AT DOOR PLEASE RECALL INSPECTION & LEAVE A MESSAGE FOR INSPECTOR. |
|
| 04/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* THERE ARE MANY CODE VIOLATIONS AND POOR WORKMANSHIP PROBLEMS WITH THIS INSTALLATION. I RECOMMEND HAVE A LICENSED ELECTRICAL CONTRACTOR GOING THROUGH THE INSTALLATION AND REPAIRING PROBLEMS PRIOR TO FINAL INSPECTION. EMT NOT ALLOWED IN EARTH DERATE CONDUCTORS AS NEEDED CHECK WIRE FILL IMPROPER PHASING (SHARED NEUTRAL) CONDUCTOR SHEATHING NEEDS TO ENTER ENCLOSURES OPEN WIRING AT SHED BRANCH CKT IDENTIFICATION TERMINATE ALL CKT NEUTRAL/GROUND SEPARATED IN SUB-PANEL GROUNDS PROPERLY TERMINATED PROPER BREAKERS FOR PANEL ETC, ETC, ETC |