Permit: T05EL02398

Parcel: 115172900


Addresses:

1765 W LINDEN ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/20/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK TO ENERGIZE SERVICE AFTER BONDING BUSHING IS INSTALLED ON SERVICE RISER.
INSTALL BONDING BUSHING ON SERVICE RISER. OK TEP RECN
12/16/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*EXTEND ROMEX SHEATHING INTO NEW PANEL
USE SQUARE D BREAKERS FOR PANEL
MAX 15 AMP FOR # 14 WIRE AND 20 AMP FOR # 12 WIRE
DO NOT INSTALL DIFFERENT WIRE SIZES UNDER SAME TERMINAL OR LUG
INSTALL MAIN BREAKER PROPERLY ON BUSS
MARK PANEL DIRECTORY.
12/07/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
1. THIS PANEL IS NOT PROPERLY ATTACHED TO STRUCTURE
2. PANEL NEEDS TO BE REPLACED OR REPAIRED - HAS CORRODED AND DAMAGE MATERIAL FOR BUSS @ METER