Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T05EL02388
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/20/2005 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* | |
12/16/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HARDWARE TO BE 1/4" MINIMUM 2) SERVICE BONDING TO BE OUTSIDE OF DISCONNECTING MEANS 3) CADWELD SPLICE TO BE EFFECTIVE 4) LABEL BREAKERS 5) PANEL AT 2ND STRUCTURE LISTED AS SERVICE EQUIPMENT ONLY. CANNOT BE USED AS A SUB-PANEL 6) TIGHTEN LOOSE FITTINGS 7) BREAKERS TO BE LISTED FOR USE BY MANUFACTURER 8) CHASE NIPPLE NOT AN APPROVED FITTING FOR USE WITH LB 9) PLEASE CORRECTLY SUPPORT ALL CONDUITS |