Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 12/22/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* SERVICE NOT GROUNDED J-BOX -MARK OUTSIDE AS 2027 & TIE # 12 GREEN WIRE TO BOX ALL CIRCUITS TO BE TESTED HAVE TO BE WIRE NUTTED OFF ALSO THIS IS FOR A RECONNECT-ALSO NEED A SERVICE UPGRADE PERMIT SINCE SERVICE WAS UPGRADED THIS WILL BE FOR TESTING POWER FOR SABINO ELECT ONLY NO OCCUPANCY. 2029 E 34TH ST AT J-BOX TIE # 12 GREEN TO BOX TAPE HOT CONDUCTOR GOING INTO HOUSE WHICH HAS INSULATION BROKEN OFF MARK BOX 2029 SEE LIST FOR 2027 E 34TH ST |