Permit: T05EL02379

Parcel: 138230710


Addresses:

634 W CALLE ARAGON

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/05/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/12/2005 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*CALL FOR FINAL AFTER TEP TIE IN
PLUG HO?E IN BACK OF PANEL.
12/09/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND GAS PIPING, WATER PIPE BOND INCORRECT METHOD OF ATTACHING #4 BARE GROUND ROD CLAMPS LOOSE, USE ACORN CLAMPS OR TURN CLAMP AROUND SO IT IS TIGHT ON ROD.
2. INSTALL BUSHING IN BACK OF NEW SERVICE PANEL TO PROTECT CABLE FROM ABRASION.