Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2005 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 11/30/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PANEL RATED 100 AMP MAX (NOT 125 MAIN) 2) INSTALL HOLDOWN ON BACK FED MAIN BREAKER 3) TIGHTEN ALL GROUNDING ELEECTRODE CONNECTIONS |