Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2005 | ELECTRIC - SERVICE RELOCATION | Approved | ||
| 12/02/2005 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999*INSTALL ADDRESS LABEL PER TEP. SPLICE NOT ACCEPTABLE AT GROUNDING ELECTRODES BOND WATER PER NEC & IRC BOND GAS PER NEC & IRC RODS TO BE DRIVEN FLUSH OR BELOW GRADE. NOTE-LIC CONTRACTOR IS REQ'D DUE TO HOUSE BEING UNOCCUPIED ( OWNER CAN ONLY WORK ON PREMISES WHEN THEY OCCUPY IT) |